EUROPEApplicable cable| Product name | Size(mm2) |
| RO-FLEX 50T | 0.5 - 2.5 |
| RO-FLEX 80T | 0.75 - 35 |
⇄ Swipe
IEC 60364-5-52
Low-voltage electrical installations –
Part 5-52: Selection and erection of electrical equipment – Wiring systems
Current carrying capacities(A)
(Ambient temperature other than 30℃) =| Size(mm2) | 2c | 3c | 4c | 5c | 6c・7c | 8‐10c | 11‐14c | 15‐20c |
| 0.5 | 6.4 | 5.6 | 5.2 | 4.8 | 4.4 | 4.0 | 3.6 | 3.2 |
| 0.75 | 8.0 | 7.0 | 6.5 | 6.0 | 5.5 | 5.0 | 4.5 | 4.0 |
⇄ Swipe
| Size(mm2) | 1 - 3c | 4 - 6c | 7 - 9c | 10 - 30c |
| 1.0 | 12 | 9.6 | 8.4 | 6.0 |
| 1.5 | 16 | 12.8 | 11.2 | 8.0 |
| 2.5 | 22 | 17.6 | 15.4 | 11 |
| 4.0 | 31 | 24 | ||
| 6.0 | 40 | 32 | ||
| 10 | 57 | 45 | ||
| 16 | 72 | 57 | ||
| 25 | 99 | 79 | ||
| 35 | 123 | 98 |
| Ambient temperature(℃) | Correction Factor |
| 10 | 1.22 |
| 11 - 15 | 1.17 |
| 16 - 20 | 1.12 |
| 21 - 25 | 1.06 |
| 26 - 30 | 1.00 |
| 31 - 35 | 0.94 |
| 36 - 40 | 0.87 |
| 41 - 45 | 0.79 |
| 46 - 50 | 0.71 |
| 51 - 55 | 0.61 |
| 56 - 60 | 0.50 |
© 2020 NICHIGOH COMMUNICATION ELECTRIC WIRE CO.,LTD. All Rights Reserved.